10.524 (ID 1797) Flux Stabilator Gain
Location in the menu:
P2.6.18.7
(Multi-purpose Control Application, VACON
®
NXP)
Use this parameter to set the gain of the flux stabilizer for induction motors.
10.525 (ID 1801) FB Fault Preset Frequency
Location in the menu:
P2.7.40
(Multi-purpose Control Application, VACON
®
NXP)
Use this parameter to set the frequency reference for the fieldbus communication warning.
This parameter shows the frequency reference value to be used when fieldbus is the active control place, if fieldbus fault is active
and the response to the fault (parameter
ID 733
) is set to 4 (Warn:PresetF).
10.526 (ID 1850) FB Fault Delay
Location in the menu:
P2.7.42
(Multi-purpose Control Application, VACON
®
NXP)
Use this parameter to set the fieldbus fault delay.
This parameter defines the time when FB fault is generated if there is Warning, if fieldbus fault is active and the response to the fault
(parameter
ID 733
) is set to 5 (Warn:PreFreq). If this time is set to zero, the drive stays in previous operation condition indefinitely.
10.527 (ID 1851) FB Fault Back Delay
Location in the menu:
P2.7.43
(Multi-purpose Control Application, VACON
®
NXP)
Use this parameter to set the fieldbus fault back delay.
This parameter defines how long frequency reference is frozen after fieldbus reconnection, if fieldbus fault is active and the re-
sponse to the fault (parameter
ID 733
) is set to 5 (Warn:PreFreq).
10.528 (ID 1857) Reset Datalogger
Location in the menu:
P2.7.44
(Multi-purpose Control Application, VACON
®
NXP)
Use this parameter to select how to reset datalogger.
This parameter can define how to reset datalogger signals.
Selection
number
Selection name Description
0
Auto
Datalogger signals are changed based on motor control mode automatically. Setting datalogger
from NCDrive disables signal change automatically, to reactivate automatic change set this pa-
rameter to 1.
1
Reset to Auto
When datalogger signals have been changed in NCDrive, use this selection to set datalogger
back to Auto mode.
2
SW Default
System software default values are activated and mode changes automatically to 4.
3
Auto Fast
Same as selection 0 but signals are recorded at fast time level. This selection increases system
load.
4
No Change
Application does not change the signal.
10.529 (ID 1900) Ramp; Skip S2
Location in the menu:
P2.4.21
(Multi-purpose Control Application)
Use this parameter to bypass the second corner S-ramp.
This function is used to bypass the second corner S-ramp (that is, to avoid the unnecessary speed increase, shown with the solid line
in
) when the reference is changed before the final speed is reached. Also S4 is bypassed when reference is increased
while speed is ramping down.
AB296635287482en-000301 / DPD00903
292 | Danfoss A/S © 2023.02
Parameter Descriptions
VACON® NX All-in-One
Application Guide