Index
Parameter
Min
Max
Unit Default ID
Description
1 = Inverted
P2.3.26
Analog output 2 minimum
0
1
-
0
475 0 = 0 mA (0 V)
1 = 4 mA (2 V)
P2.3.27
Analog output 2 scaling
10
1000
%
1.00
476 -
1
Use the Terminal to Function method (TTF) with these parameters, see
10.626 "Terminal to Function" (TTF) Programming Principle
.
6.4.5 Drive Control Parameters (Control Panel: Menu M2 -> G2.4)
Table 39: Drive Control Parameters, G2.4
Index
Parameter
Min Max
Unit Default ID
Description
P2.4.1
Ramp 1 shape
0.0
10.0
s
0.1
500 0 = Linear
>0 = S-curve ramp time
P2.4.2
Ramp 2 shape
0.0
10.0
s
0.0
501 0 = Linear
>0 = S-curve ramp time
P2.4.3
Acceleration time 2
0.1
3000.0 s
1.0
502 -
P2.4.4
Deceleration time 2
0.1
3000.0 s
1.0
503 -
P2.4.5
Brake chopper
0
4
-
0
504 0 = Disabled
1 = Used when running
2 = External brake chopper
3 = Used when stopped/running
4 = used when running (no testing)
P2.4.6
Start function
0
2
-
0
505 0 = Ramp
1 = Flying start
2 = Conditional flying start
P2.4.7
Stop function
0
3
-
0
506 0 = Coasting
1 = Ramp
2 = Ramp+Run enable coast
3 = Coast+Run enable ramp
P2.4.8
DC braking current
0.00 I
L
A
0.7 x I
H
507 -
P2.4.9
DC braking time at stop
0.00 600.00 s
0.00
508 0 = DC brake is off at stop
P2.4.10 Frequency to start DC braking during
ramp stop
0.10 10.00
Hz
1.50
515 -
P2.4.11 DC braking time at start
0.00 600.00 s
0.00
516 0 = DC brake is off at start
P2.4.12 Flux brake
0
1
-
0
520 0 = Off
AB296635287482en-000301 / DPD00903 | 71
Danfoss A/S © 2023.02
PID Control Application
VACON® NX All-in-One
Application Guide