Index
Parameter
Min
Max
Unit Default ID
Description
P2.3.10
Output frequency limit 1 su-
pervision
0
2
-
0
315 0 = No limit
1 = Low limit supervision
2 = High limit supervision
P2.3.11
Output frequency limit 1; Su-
pervised value
0.00
320.00 Hz
0.00
316 -
P2.3.12
Output frequency limit 2 su-
pervision
0
2
-
0
346 0 = No limit
1 = Low limit supervision
2 = High limit supervision
P2.3.13
Output frequency limit 2; Su-
pervision value
0.00
320.00 Hz
0.00
347 -
P2.3.14
Torque limit supervision func-
tion
0
2
-
0
348 0 = No
1 = Low limit
2 = High limit
P2.3.15
Torque limit supervision value
-300.0 300.0
%
0.0
349 -
P2.3.16
Reference limit supervision
function
0
2
-
0
350 0 = No
1 = Low limit
2 = High limit
P2.3.17
Reference limit supervision
value
0.0
100.0
%
0.0
351 -
P2.3.18
External brake Off-delay
0.0
100.0
s
0.5
352 -
P2.3.19
External brake On-delay
0.0
100.0
s
1.5
353 -
P2.3.20
Frequency converter tempera-
ture limit supervision
0
2
-
0
354 0 = No
1 = Low limit
2 = High limit
P2.3.21
Frequency converter tempera-
ture limit value
-10
100
°C
40
355 -
P2.3.22
(1)
Analog output 2 scaling
0.1
E.10
-
0.1
471 -
P2.3.23
(1)
Analog output 2 function
0
8
-
4
472 As parameter 2.3.2
P2.3.24
(1)
Analog output 2 filter time
0.00
10.00
s
1.00
473 0 = No filtering
P2.3.25
(1)
Analog output 2 inversion
0
1
-
0
474 0 = Not inverted
1 = Inverted
P2.3.26
(1)
Analog output 2 minimum
0
1
-
0
475 0 = 0 mA (0 V)
AB296635287482en-000301 / DPD00903 | 53
Danfoss A/S © 2023.02
Multi-step Speed Control
Application
VACON® NX All-in-One
Application Guide
Summary of Contents for VACON NX
Page 1: ...Application Guide VACON NX All in One drives danfoss com...
Page 2: ......