Index
Parameter
Min
Max
Unit
Default
ID
Description
1 = Speed control
P2.6.2
(1)
U/f optimisation
0
1
-
0
109
0 = Not used
1 = Automatic torque boost
P2.6.3
(1)
U/f ratio selection
0
3
-
0
108
0 = Linear
1 = Squared
2 = Programmable
3 = Linear with flux optim.
P2.6.4
(1)
Field weakening point
8.00
320.00
Hz
50.00
602
-
P2.6.5
(1)
Voltage at field weakening point
10.00
200.00
%
100.00
603
-
P2.6.6
(1)
U/f curve midpoint frequency
0.00
P2.6.4
Hz
50.00
604
-
P2.6.7
(1)
U/f curve midpoint voltage
0.00
100.00
%
100.00
605
-
P2.6.8
(1)
Output voltage at zero frequency
0.00
40.00
%
Varies
606
-
P2.6.9
Switching frequency
1.0
Varies
kHz
Varies
601
P2.6.10
Overvoltage controller
0
2
-
1
607
0 = Not used
1 = Used (no ramping)
2 = Used (ramping)
P2.6.11
Undervoltage controller
0
2
-
1
608
0 = Not used
1 = Used
2 = Used (ramping to zero)
P2.6.12
Identification
0
4
-
0
631
0 = No action
1 = Identification w/o run
2 = Identification with run
3 = Encoder ID Run (PMSM)
4 = Ident All
1
Use the Terminal to Function method (TTF) with these parameters, see
10.626 "Terminal to Function" (TTF) Programming Principle
).
8.4.8 Protections (Control Panel: Menu M2 -> G2.7)
Table 106: Protections, G2.7
Index
Parameter
Min
Max
Unit
Default
ID
Description
P2.7.1
Response to 4 mA reference fault
0
5
-
4
700
0 = No response
1 = Warning
2 = Previous Freq.
3 = Wrng+Preset- Freq 2.7.2
4 = Fault, stop acc. to 2.4.7
5 = Fault, stop by coasting
P2.7.2
4 mA reference fault frequency
0.00
P2.1.2
Hz
0.00
728
-
AB296635287482en-000301 / DPD00903 | 145