Use this parameter to set the level of flux as a percentage of the nominal flux voltage.
Motor voltage corresponding to 110% of flux as a percentage of nominal flux voltage.
10.497 (ID 1366) Flux 120%
Location in the menu:
P2.6.18.12
(Multi-purpose Control Application, VACON
®
NXS)
P2.6.17.12
(Multi-purpose Control Application, VACON
®
NXP)
Use this parameter to set the level of flux as a percentage of the nominal flux voltage.
Motor voltage corresponding to 120% of flux as a percentage of nominal flux voltage.
10.498 (ID 1367) Flux 130%
Location in the menu:
P2.6.18.13
(Multi-purpose Control Application, VACON
®
NXS)
P2.6.17.13
(Multi-purpose Control Application, VACON
®
NXP)
Use this parameter to set the level of flux as a percentage of the nominal flux voltage.
Motor voltage corresponding to 130% of flux as a percentage of nominal flux voltage.
10.499 (ID 1368) Flux 140%
Location in the menu:
P2.6.18.14
(Multi-purpose Control Application, VACON
®
NXS)
P2.6.17.14
(Multi-purpose Control Application, VACON
®
NXP)
Use this parameter to set the level of flux as a percentage of the nominal flux voltage.
Motor voltage corresponding to 140% of flux as a percentage of nominal flux voltage.
10.500 (ID 1369) Flux 150%
Location in the menu:
P2.6.18.15
(Multi-purpose Control Application, VACON
®
NXS)
P2.6.17.15
(Multi-purpose Control Application, VACON
®
NXP)
Use this parameter to set the level of flux as a percentage of the nominal flux voltage.
Motor voltage corresponding to 150% of flux as a percentage of nominal flux voltage.
10.501 (ID 1385) ID Bit Free DO2
Location in the menu:
P2.3.2.6
(Multi-purpose Control Application)
Use this parameter to select the signal that controls the digital output.
Set the parameter in format xxxx.yy where xxxx is the ID number of a signal and yy is the bit number. For example, the value for DO
control is 43.06. 43 is the ID number of Status Word. So the digital output is ON when bit number 06 of Status Word (ID number 43)
that is, Run Enable is on.
10.502 (ID 1401) Stop State Flux
Location in the menu:
P2.6.15.24
(Multi-purpose Control Application, VACON
®
NXP)
Use this parameter to set the flux that is kept in the motor after the AC drive stops.
The flux is maintained for the time set by parameter
ID 1402
. This parameter can be used in closed loop motor control mode only.
10.503 (ID 1402) Flux Off Delay
Location in the menu:
P2.6.15.23
(Multi-purpose Control Application, VACON
®
NXP)
Use this parameter to set the time for how long the Stop State Flux is kept in the motor after the AC drive stops.
AB296635287482en-000301 / DPD00903
288 | Danfoss A/S © 2023.02
Parameter Descriptions
VACON® NX All-in-One
Application Guide