Illustration 62: Scaling of DC-Braking Current
A
DC-braking current
B
Signal range
C
Free analogue input
10.145 (ID 401) Scaling of Acceleration and Deceleration Times
Location in the menu:
P2.2.6.3
(Multi-purpose Control Application)
Use this parameter to select the signal to adjust the acceleration and deceleration times.
See parameter
ID 399
.
Acceleration and deceleration times can be reduced with the free analog input signal according to the following formulas:
Reduced time = set acc./deceler. time (parameters
ID 103
,
ID 104
;
ID 502
,
ID 503
) divided by the factor R from
.
Analog input level zero corresponds to ramp times set by parameters. Maximum level is a tenth of value set by parameter.
10
2
1
0
e
3
0
b
h
0
4
5
.1
0
A
C
B
Illustration 63: Reducing of Acceleration and Deceleration Times
A
Factor R
B
Signal range
C
Free analogue input
10.146 (ID 402) Scaling of Torque Supervision Limit
Location in the menu:
P2.2.6.4
(Multi-purpose Control Application)
Use this parameter to select the signal to adjust the torque supervision limit.
See
ID 399
.
The set torque supervision limit can be reduced with the free analog input signal between 0 and the set supervision limit,
ID 349
.
AB296635287482en-000301 / DPD00903 | 215
Danfoss A/S © 2023.02
Parameter Descriptions
VACON® NX All-in-One
Application Guide