Table 76: Open Loop Parameters, G2.6.14
Index
Parameter
Min
Max
Unit Default
ID
Description
P2.6.14.1
U/f Optimization
0
1
-
0
109
0 = Not used
1 = Automatic torque boost
P2.6.14.2
U/f Ratio Select
0
3
-
0
108
0 = Linear
1 = Squared
2 = Programmable
3 = Linear with flux optim.
P2.6.14.3
Field Weakening Point
8.00
320.00
Hz
50.00
602
-
P2.6.14.4
Voltage at Field Weakening Point
10.00
200.00
%
100.00
603
-
P2.6.14.5
U/f curve midpoint frequency
0.00
P2.6.14.4
Hz
50.00
604
-
P2.6.14.6
U/f curve midpoint voltage
0.00
100.00
%
100.00
605
-
P2.6.14.7
Output voltage at zero frequency
0.00
40.00
-
Varies
606
-
P2.6.14.8
Speed controller P gain (open loop)
0
32767
-
3000
637
-
P2.6.14.9
Speed controller I gain (open loop)
0
32767
-
300
638
-
P2.6.14.10
Enable I/f control
0
1
-
0
534
-
P2.6.14.11
I/f Control limit
0.0
300.0
%
10.0
1790
-
P2.6.14.12
I/f current
0.0
150.0
%
50.0
1693
-
Table 77: Closed Loop Parameters, G2.6.15
Index
Parameter
Min
Max
Unit
Default
ID
Description
P2.6.15.1
Magnetizing current
0.00
2 x I
H
A
0.00
612
-
P2.6.15.2
Speed control P
1
1000
-
30
613
-
P2.6.15.3
Speed control I time
-32000
32000
ms
100.00
614
-
P2.6.15.5
Acceleration compensation
0.00
300.00
s
0.00
626
-
P2.6.15.6
Slip adjust
0
500
%
75
619
-
P2.6.15.7
Magnetizing current at start
0
I
L
A
0.00
627
-
P2.6.15.8
Magnetizing time at start
0
60000
ms
0
628
-
P2.6.15.9
0-speed time at start
0
32000
ms
100
615
-
P2.6.15.10
0-speed time at stop
0
32000
ms
100
616
-
P2.6.15.11
Start-up torque
0
3
-
0
621
0 = Not used
AB296635287482en-000301 / DPD00903 | 109
Danfoss A/S © 2023.02
Multi-purpose Control Application
VACON® NX All-in-One
Application Guide
Summary of Contents for VACON NX
Page 1: ...Application Guide VACON NX All in One drives danfoss com...
Page 2: ......