This monitoring value shows the actual speed of the motor that is sent to the fieldbus.
9.88 (ID 875) FB Speed Reference
Location in the menu:
V1.22.2
(Multi-Purpose Control Application in VACON
®
NXP only)
This monitoring value shows the fieldbus frequency reference as a percentage of minimum frequency to maximum frequency.
9.89 (ID 1113) Current
Location in the menu:
V1.21.1
(Multi-Purpose Control Application in VACON
®
NXP only)
V1.26.1
(PID Control Application, Pump and Fan Control Application)
This monitoring value shows the unfiltered motor current.
9.90 (ID 1124) Encoder 1 Frequency
Location in the menu:
V1.21.5
(Multi-Purpose Control Application in VACON
®
NXP only)
This monitoring value shows the input frequency of the encoder.
9.91 (ID 1125) Torque
Location in the menu:
V1.21.2
(Multi-Purpose Control Application)
V1.26.2
(PID Control Application, Pump and Fan Control Application)
This monitoring value shows the unfiltered motor torque.
9.92 (ID 1131) Final Frequency Reference
Location in the menu:
V1.21.22
(Multi-Purpose Control Application in VACON
®
NXP only)
This monitoring value shows the final shaft frequency reference for the speed controller.
9.93 (ID 1132) Step Response
Location in the menu:
V1.21.23
(Multi-Purpose Control Application in VACON
®
NXP only)
This monitoring value shows the response for the frequency ramp step.
9.94 (ID 1140) FB Torque Reference
Location in the menu:
V1.22.4
(Multi-Purpose Control Application in VACON
®
NXP only)
This monitoring value shows the fieldbus torque reference.
9.95 (ID 1160) Fieldbus Control Word
Location in the menu:
V1.22.1
(Multi-Purpose Control Application in VACON
®
NXP only)
This monitoring value shows the status of the fieldbus control word that the application uses in bypass mode.
Depending on the fieldbus type or profile, the data that is received from the fieldbus can be modified before it is sent to the applica-
tion.
Table 110: Fieldbus Control Word (ProfiDrive)
Bit
Value = 0 (FALSE)
Value = 1 (TRUE)
Bit 0
OFF
ON, Reset after Fault or b1 and b2
Bit 1
Emergency stop by coast
ON, On normal operation: Keep TRUE
Bit 2
Emergency stop by ramp
ON, On normal operation: Keep TRUE
Bit 3
STOP REQUEST
RUN REQUEST
Bit 4
Force ramp to Zero
Enable Ramp
Bit 5
Freeze Ramp
Enable Ramp
AB296635287482en-000301 / DPD00903 | 159
Danfoss A/S © 2023.02
Monitoring Value Descriptions
VACON® NX All-in-One
Application Guide