2 = Fault, stop by coasting
P2.7.37
TBoard2 Numbers
0
5
-
0
743
0 = Not used
1 = Channel 1
2 = Channel 1 & 2
3 = Channel 1 & 2 & 3
4 = Channel 2 & 3
5 = Channel 3
P2.7.38
TBoard2 Warn.Lim
-30.0
200.0
Cº
120
745
-
P2.7.39
TBoard2 Flt.Lim
-30.0
200.0
Cº
130
746
-
P2.7.40
FB Fault Freq
0
P2.1.2
Hz
20.00
1801 -
P2.7.41
ActiveFilt.Fault
0
3
-
2
776
0=No response
1 = Warning
2 = Fault
3=Fault, coast
P2.7.42
FB Fault Delay
0
60.0
s
0.5
1850 -
P2.7.43
FB Fault Back Delay
0
60.0
s
10.0
1851 -
P2.7.44
Reset Datalogger
0
4
-
4
1857 0 = Auto
1 = Reset to Auto
2 = SW Default
3 = Auto Fast
4 = No Change
P.2.7.45 Quick Stop Indication
0
2
-
1
1543 0 = No response
1 = Warning
2 = Fault
P2.7.46
External Fault 2
0
3
-
2
747
0 = No Response
1 = Warning
2 = Fault, stop acc. to P2.4.7
3 = Fault, stop by coasting
P2.7.47
Run Enable Indication
0
2
-
0
1177 0 = No Action
1 = Warning
2 = Fault
2.7.48
Cooling Fault Response
0
3
-
2
762
0 = Stop state: No Action, Run state: Warning
1 = Stop state: Warning, Run state: Warning
2 = Stop state: Warning, Run state: Fault
3 = Stop state: No Action, Run state: Fault
2.7.49
Fault Warning Indication
0
2
-
0
1940 0 = Static
1 = Toggle
2 = Marine
AB296635287482en-000301 / DPD00903 | 117
Danfoss A/S © 2023.02
Multi-purpose Control Application
VACON® NX All-in-One
Application Guide