Index
Parameter
Min
Max
Unit Default ID
Description
3 = Fault, stop by coasting
P2.7.22
Response to fieldbus fault
0
5
-
2
733
0 = No response
1 = Warning
2 = Fault, stop acc. to 2.4.7
3 = Fault, stop by coasting
4 = Warning, preset Frequency
5 = Warning, previous Frequency
P2.7.23
Response to slot fault
0
3
-
2
734
See P2.7.21
P2.7.24
TBoard1 Numbers
0
5
-
0
739
0 = Not used
1 = Channel 1
2 = Channel 1 & 2
3 = Channel 1 & 2 & 3
4 = Channel 2 & 3
5 = Channel 3
P2.7.25
TBoard Flt. Resp
0
3
-
0
740
0 = No response
1 = Warning
2 = Fault,stop acc. to 2.4.7
3 = Fault,stop by coasting
P2.7.26
TBoard1 Warn.Lim
-30.0
200.0
ºC
120.0
741
-
P2.7.27
TBoard1 Flt.Lim
-30.0
200.0
ºC
130.0
742
-
P2.7.28
Brake fault action
1
3
-
1
1316 1 = Warning
2 = Fault, stop acc. to 2.4.7
3 = Fault, stop by coasting
P2.7.29
Brake fault delay
0.00
320.00 s
0.20
1317 -
P2.7.30
System bus fault
0
3
-
3
1082 0 = No response
1 = Warning
2 = Fault, stop acc. to 2.4.7
3 = Fault, stop by coasting
P2.7.31
System bus fault delay
0.00
10.00
s
3.00
1352 -
P2.7.32
Cooling fault delay
0.00
7.00
s
2.00
751
-
P2.7.33
Speed error mode
0
2
-
0
752
0 = No response
1 = Warning
2 = Fault, stop by coasting
P2.7.34
Speed error maximum dif-
ference
0
100
%
5
753
-
P2.7.35
Speed error fault delay
0.00
100.00 s
0.50
754
-
P2.7.36
Safe disable mode
0
2
-
1
755
1 = Warning, stop by coasting
AB296635287482en-000301 / DPD00903
116 | Danfoss A/S © 2023.02
Multi-purpose Control Application
VACON® NX All-in-One
Application Guide