Index
Parameter
Min
Max
Unit
Default
ID
Description
P2.6.8
Output voltage at zero frequency
0.00
40.00
%
Varies
606
-
P2.6.9
Switching frequency
1.0
Varies
kHz
Varies
601
-
P2.6.10
Overvoltage controller
0
2
-
1
607
0 = Not used
1 = Used (no ramping)
2 = Used (ramping)
P2.6.11
Undervoltage controller
0
2
-
1
608
0 = Not used
1 = Used
2 = Used (ramping to zero)
P2.6.12
Motor control mode 2
0
4
-
2
521
See P2.6.1
P2.6.13
Speed controller P gain (open loop)
0
32767
-
3000
637
-
P2.6.14
Speed controller I gain (open loop)
0
32767
-
300
638
-
P2.6.15
Load drooping
0.00
100.00
%
0.00
620
-
P2.6.16
Identification
0
1
-
0
631
0 = No action
1 = Identification w/o run
Table 73: Closed Loop Parameters, VACON
®
NXS (Control Panel: Menu M2 ->G2.6.23)
Index
Parameter
Min
Max
Unit
Default
ID
Description
P2.6.17.1
Magnetizing current
0.00
2 x I
H
A
0.00
612
-
P2.6.17.2
Speed control P
1
1000
-
30
613
-
P2.6.17.3
Speed control I time
-3200.0
3200.0
ms
100.0
614
-
P2.6.17.5
Acceleration compensation
0.00
300.00
s
0.00
626
-
P2.6.17.6
Slip adjust
0
500
%
75
619
-
P2.6.17.7
Magnetizing current at start
0.00
I
L
A
0.00
627
-
P2.6.17.8
Magnetizing time at start
0
32000
ms
0
628
-
P2.6.17.9
0-speed time at start
0
32000
ms
100
615
-
P2.6.17.10
0-speed time at stop
0
32000
ms
100
616
-
P2.6.17.11
Start-up torque
0
3
-
0
621
0 = Not used
1 = Torque memory
2 = Torque reference
3 = Start-up torque fwd/rev
P2.6.17.12
Start-up torque FWD
-300.0
300.0
s
0.0
633
-
AB296635287482en-000301 / DPD00903
106 | Danfoss A/S © 2023.02
Multi-purpose Control Application
VACON® NX All-in-One
Application Guide