7.2 Control I/O in Multi-purpose Control Application
1
6
2
3
4
5
18
19
20
12
7
13
8
9
10
14
15
16
21
22
23
11
17
24
25
26
e3
0b
h0
94
.2
0
mA
RUN
READY
AO1-
DO1
+24 V
GND
GND
DIN1
DIN2
DIN3
DIN4
DIN5
DIN6
RO1
RO1
RO1
CMA
CMB
RO2
RO2
RO2
OPTA1
OPTA2 / OPTA3
Terminal
Signal
Description
+10 V
ref
AI1+
AI1-
AI2+
AI2-
+24V
Reference output
I/O Ground
Analogue input 2
Current range 0—20mA
Control voltage output
I/O ground
Start forward
Programmable logic (P2.2.1.1)
Start reverse
R
i
min = 5 kΩ
Fault reset
Programmable (G2.2.7)
Jogging speed selection
Programmable (G2.2.7)
External fault
Programmable (G2.2.7)
Accel. /decel. time select
Programmable (G2.2.7)
Common for DIN 1—DIN 3
Common for DIN4—DIN6
Control voltage output
I/O ground
Analogue output 1
Output frequency
Programmable (P2.3.5.2)
Digital output
READY
Programmable (G2.3.3)
Open collector,
I≤50 mA, U≤48 VDC
Relay output 1
RUN
Programmable
(G2.3.3)
Relay output 2
FAULT
Programmable
(G2.3.3)
Range 0—20 mA/R
L
,
max. 500 Ω
AO1+
Analogue input 1
frequency reference
Ground for reference
and controls
Analogue input 2
frequency reference
Contact closed = start forward
Contact closed = start reverse
Contact closed (rising edge) = fault
reset
Contact open = P2.1.3, and P2.1.4
in use Contact closed = P2.4.3., and
P2.4.4 in use
Contact open = no fault
Contact closed = external fault
Contact open = IO reference active
Contact closed
= Jogging speed active
Voltage for potentiometer, etc.
Analogue input 1
Voltage range 0—10V DC
Programmable (P2.1.11)
Voltage for switches,
etc. max 0.1 A
Voltage for switches (see #6)
Ground for reference and controls
Connect to GND or +24 V
Connect to GND or +24 V
Ground for reference and controls
Reference potentiometer,
1-10kΩ
Illustration 17: Default I/O Configuration in Multi-purpose Control Application
The option board OPTA3 has no terminal for open contact on its second relay output (terminal 24 is missing).
See jumper selections in
. More information in the User Manual of the product.
AB296635287482en-000301 / DPD00903
78 | Danfoss A/S © 2023.02
Multi-purpose Control Application
VACON® NX All-in-One
Application Guide
Summary of Contents for VACON NX
Page 1: ...Application Guide VACON NX All in One drives danfoss com...
Page 2: ......