Index
Parameter
Min
Max
Unit Default ID
Description
P2.2.7
AI1 signal inversion
0
1
-
0
323 0 = Not inverted
1 = Inverted
P2.2.8
AI1 signal filter time
0.00
10.00
s
0.10
324 -
P2.2.9
(2)
AI2 signal selection
0.1
E.10
-
A.2
388 -
P2.2.10
(3)
AI2 signal range
0
2
-
1
325 0 = 0–10 V (0–20 mA)
1 = 2–10 V (4–20 mA)
2 = Custom setting range
P2.2.11
AI2 custom setting mini-
mum
-160.00 160.00 %
0.00
326 -
P2.2.12
AI2 custom setting maxi-
mum
-160.00 160.00 %
100.00
327 -
P2.2.13
AI2 signal inversion
0
1
-
0
328 0 = Not inverted
1 = Inverted
P2.2.14
AI2 signal filter time
0.00
10.00
s
0.10
329 -
P2.2.15
Reference scaling mini-
mum value
0.00
320.00 Hz
0.00
303 -
P2.2.16
Reference scaling maxi-
mum value
0.00
320.00 Hz
0.00
304 -
P2.2.17
Free analog input, signal
selection
0
2
-
0
361 0 = Not used
1 = Analog input 1
2= Analog input 2
P2.2.18
Free analog input, function 0
4
-
0
362 0 = No reset
1 = Reduces current limit (P2.1.5)
2 = Reduces DC braking current, P2.4.8
3 = Reduces accel. and decel. times
4 = Reduces torque supervision limit, P2.3.15
1
Parameter value can only be changed after the AC drive has been stopped.
2
Use the Terminal to Function method (TTF) with these parameters, see
10.626 "Terminal to Function" (TTF) Programming Principle
.
3
Remember to place jumpers of block X2 according to the selection (0, 1 or 2). See the User Manual of the product.
CP = control place
cc = closing contact
oc = opening contact
AB296635287482en-000301 / DPD00903 | 51
Danfoss A/S © 2023.02
Multi-step Speed Control
Application
VACON® NX All-in-One
Application Guide