Index
Parameter
Min
Max
Unit
Default
ID
Description
P2.2.2.9
AI1 sleep limit
0.00
100.00
%
0.00
385
-
P2.2.2.10
AI1 sleep delay
0.00
320.00
s
0.00
386
-
P2.2.2.11
AI1 joystick offset
-100.00
100.00
%
0.00
165
-
1
Use the Terminal to Function method (TTF) with these parameters, see
10.626 "Terminal to Function" (TTF) Programming Principle
2
Remember to place jumpers of block X2 according to the selection (0, 1, 2, or 3). See the User Manual of the product.
Table 58: Analog Input 2 (Control Panel: Menu M2 -> G2.2.3)
Index
Parameter
Min
Max
Unit
Default
ID
Description
P2.2.3.1
(1)
AI2 signal selection
0.1
E.10
-
A.2
388
-
P2.2.3.2
AI2 filter time
0.00
320.00
s
0.10
329
-
P2.2.3.3
(2)
AI2 signal range
0
3
-
1
325
0 = 0–10 V (0-20mA)
1 = 2–10 V (4–20 mA)
2 = -10V...+10 V
3 = Custom range
P2.2.3.4
AI2 custom minimum setting
-160.00
160.00
%
20.00
326
-
P2.2.3.5
AI2 custom maximum setting
-160.00
160.00
%
100.00
327
-
P2.2.3.6
AI2 reference scaling, minimum value
0.00
320.00
Hz
0.00
393
-
P2.2.3.7
AI2 reference scaling, maximum value
0.00
320.00
Hz
0.00
394
-
P2.2.3.8
AI2 joystick hysteresis
0.00
20.00
%
0.00
395
-
P2.2.3.9
AI2 sleep limit
0.00
100.00
%
0.00
396
-
P2.2.3.10
AI2 sleep delay
0.00
320.00
s
0.00
397
-
P2.2.3.11
AI2 joystick offset
-100.00
100.00
%
0.00
166
-
1
Use the Terminal to Function method (TTF) with these parameters, see
10.626 "Terminal to Function" (TTF) Programming Principle
2
Remember to place jumpers of block X2 according to the selection (0, 1, 2 or 3). See the User Manual of the product.
Table 59: Analog Input 3 (Control Panel: Menu M2 -> G2.2.4)
Index
Parameter
Min
Max
Unit
Default
ID
Description
P2.2.4.1
(1)
AI3 signal selection
0.1
E.10
-
0.1
141
-
P2.2.4.2
AI3 filter time
0.00
320.00
s
0.00
142
0 = No filtering
P2.2.4.3
(2)
AI3 signal range
0
3
-
0
143
0 = 0–10 V (0-20mA)
1 = 2–10 V (4–20 mA)
2 = -10V...+10 V
AB296635287482en-000301 / DPD00903
94 | Danfoss A/S © 2023.02
Multi-purpose Control Application
VACON® NX All-in-One
Application Guide
Summary of Contents for VACON NX
Page 1: ...Application Guide VACON NX All in One drives danfoss com...