Selection number
Selection name
Run state: Fault
10.381 (ID 776) Response to Active Filter Fault
Location in the menu:
P2.7.41
(Multi-purpose Control Application, VACON
®
NXP)
Use this parameter to set the fault response for the active filter fault.
This parameter defines the response to be triggered when the active filter fault input (set with parameter
ID 214
) is closed.
See separate VACON
®
NX OPTAF (STO) Board Manual for detailed information on the Safe Disable function. This function is available
only if the drive is equipped with VACON
®
option board OPTAF.
Selection number
Selection name
Description
0
No Action
No response
1
Warning
Warning
2
Fault
Fault, stop at fault according to parameter ID 506.
3
Fault, Coast
Fault, stop at fault always by coasting.
This parameter is present in VACON
®
NXP drives only.
10.382 (ID 784) Ambient Temperature Response
Location in the menu:
P2.7.51
(Multi-purpose Control Application, VACON
®
NXP)
Use this parameter to select the response for the ambient temperature digital input.
Selection number
Selection name
0
No Action
1
Warning
2
Fault
10.383 (ID 785) Input Switch Response
Location in the menu:
P2.7.52
(Multi-purpose Control Application, VACON
®
NXP)
Use this parameter to select the response for the input switch digital input.
Selection number
Selection name
0
No Action
1
Warning
2
Fault
10.384 (ID 850) Fieldbus Reference Minimum Scaling
Location in the menu:
P2.9.1
(Multi-purpose Control Application)
Use this parameter to set scaling to the fieldbus reference signal.
See
10.385 (ID 851) Fieldbus Reference Maximum Scaling
10.385 (ID 851) Fieldbus Reference Maximum Scaling
Location in the menu:
P2.9.2
(Multi-purpose Control Application)
Use this parameter to set scaling to the fieldbus reference signal.
If both parameters (
ID 850
&
ID 851
) have the same value, the minimum and maximum frequency limits are used for scaling.