10.590 (ID 3560) Vibration Warning S2 Delay
Location in the menu:
P2.13.4.3.6
(Multi-purpose Control Application)
Use this parameter to define how long time the actual value must be above the warning S2 notification level to trigger the warning
S2. This level is not used when delay is zero.
10.591 (ID 3561) Vibration Alarm/Fault Mode
Location in the menu:
P2.13.4.3.7
(Multi-purpose Control Application)
Use this parameter to select the alarm/fault mode which is used for calculating alarm/fault notification threshold.
Selection number
Selection name
Description
0
Absolute
Absolute value is considered as threshold
1
Offset
Calculates threshold as sum of the computed baseline data and the offset values
2
Factor
Calculates threshold as baseline data factor
10.592 (ID 3562) Vibration Alarm/Fault High
Location in the menu:
P2.13.4.3.8
(Multi-purpose Control Application)
Use this parameter to set the threshold value for computing the alarm/fault high notification threshold. Threshold value range var-
ies based on warning mode selection. This limit is not used when value is zero.
10.593 (ID 3563) Vibration Alarm/Fault Delay
Location in the menu:
P2.13.4.3.9
(Multi-purpose Control Application)
Use this parameter to define how long time the actual value must be above the alarm/fault notification level to trigger the alarm/
fault. This level is not used when delay is zero.
10.594 (ID 3564) Vibration Warning S1 Counter
Location in the menu:
P2.13.4.4.1
(Multi-purpose Control Application)
Use this parameter to set warning S1 counter value.
10.595 (ID 3565) Vibration Warning S2 Counter
Location in the menu:
P2.13.4.4.2
(Multi-purpose Control Application)
Use this parameter to set warning S2 counter value.
10.596 (ID 3566) Vibration Alarm/Fault Counter
Location in the menu:
P2.13.4.4.3
(Multi-purpose Control Application)
Use this parameter to set alarm/fault counter value.
10.597 (ID 3567) Load Mean Factor
Location in the menu:
P2.13.5.1.1
(Multi-purpose Control Application)
The several statistical data points (mean, minimum, maximum, and standard) from the baseline model can be combined into one
threshold value. Use this parameter to set the mean factor in the threshold value. If the threshold value is zero, the mean factor is
not used.
See the formula in
10.544 (ID 3511) Current Mean Factor
.
10.598 (ID 3568) Load Min Factor
Location in the menu:
P2.13.5.1.2
(Multi-purpose Control Application)
The several statistical data points (mean, minimum, maximum, and standard) from the baseline model can be combined into one
threshold value. Use this parameter to set the min factor in the threshold value. If the threshold value is zero, the min factor is not
used.
See the formula in
10.544 (ID 3511) Current Mean Factor
.
AB296635287482en-000301 / DPD00903
302 | Danfoss A/S © 2023.02
Parameter Descriptions
VACON® NX All-in-One
Application Guide