Setting value
Signal content
12 = Motor regulator activated
One of the limit regulators (for example, current limit, torque limit) is activated.
13 = Output frequency limit 1 supervision
The output frequency goes outside the set supervision low limit/ high limit (see
10.75 (ID 315) Output Frequency Limit Supervision Function
put Frequency Limit Supervision Value
).
14 = Control from I/O terminals
(1)
I/O control mode selected (in menu
M3
)
14 = Output frequency limit 2 supervi-
sion
(2)
The output frequency goes outside the set supervision low limit/ high limit (see
10.104 (ID 346) Output Frequency Limit 2 Supervision Function
and
Output Frequency Limit 2 Supervision Value
).
15 = Thermistor fault or warning
(1)
The thermistor input of option board indicates motor overtemperature. Fault or
warning depending on parameter ID 732.
15 = Torque limit supervision
(2)
The motor torque goes beyond the set supervision low limit/high limit (parameters
ID 348 and ID 349).
16 = Fieldbus DIN 1
(1)
Fieldbus digital input 1. See fieldbus manual.
16 = Reference limit supervision
Active reference goes beyond the set supervision low limit/high limit (parameters ID
350 and ID 351).
17 = External brake control
(2)
External brake ON/OFF control with programmable delay (parameters ID 352 and ID
353)
18 = Control from I/O terminals
(2)
External control mode (Menu
M3
; ID 125)
19 = AC drive temperature limit supervi-
sion
(2)
The AC drive heat sink temperature goes beyond the set supervision limits (parame-
ters ID 354 and ID 355).
20 = Unrequested rotation direction
(3)
Rotation direction is different from the requested one.
20 = Reference inverted
(4)
Rotation direction is different from the requested one.
21 = External brake control inverted
(2)
External brake ON/OFF control (parameters ID 352 and ID 353); Output active when
brake control is OFF.
22 = Thermistor fault or warning
(2)
The thermistor input of option board indicates motor overtemperature. Fault or
warning depending on parameter ID 732.
23 = Fieldbus DIN 1
(5)
Fieldbus digital input 1. See fieldbus manual.
23 = Analogue input supervision
(4)
Selects the analog input to be monitored. See
10.114 (ID 356) Analog Supervision
,
10.115 (ID 357) Analog Supervision Low Limit
10.207 (ID 463) Analog Input Supervision Limit
24 = Fieldbus DIN 1
(4)
Fieldbus digital input 1. See fieldbus manual.
25 = Fieldbus DIN 2
(4)
Fieldbus digital input 1. See fieldbus manual.
26 = Fieldbus DIN 3
(4)
Fieldbus digital input 1. See fieldbus manual.
27 = Temp.Warning
(4)
-
1
Standard Application
2
Local/Remote Control Application, Multi-Step Speed Control Application, PID Control Application, Multi-Purpose Control Application
3
Local/Remote Control Application, Multi-Step Speed Control Application, PID Control Application
4
Multi-Purpose Control Application
5
PID Control Application
AB296635287482en-000301 / DPD00903 | 191
Danfoss A/S © 2023.02
Parameter Descriptions
VACON® NX All-in-One
Application Guide