Index
Parameter
Min
Max
Unit Default ID
Description
6 = Used when running (Test only in ready
state)
P2.4.6
Start function
0
2
-
0
505
0 = Ramp
1 = Flying start
2 = Conditional flying start
P2.4.7
Stop function
0
3
-
0
506
0 = Coasting
1 = Ramp
2 = Ramp+Run enable coast
3 = Coast+Run enable ramp
P2.4.8
DC braking current
0.00
I
L
A
0.7 x I
H
507
-
P2.4.9
DC braking time at stop
0.00
600.00 s
0.00
508
0 = DC brake is off at stop
P2.4.10
Frequency to start DC brak-
ing during ramp stop
0.10
10.00
Hz
1.50
515
-
P2.4.11
DC braking time at start
0.00
600.00 s
0.00
516
0 = DC brake is off at start
P2.4.12
Flux brake
0
1
-
0
520
0 = Off
1 = On
P2.4.13
Flux braking current
0.00
I
L
A
I
H
519
-
VACON
®
NXP drives only
P2.4.14
DC-brake current at stop
0
I
L
A
0.1 x I
H
1080 -
P2.4.15
Inching reference 1
-320.00 320.00 Hz
2.00
1239 -
P2.4.16
Inching reference 2
-320.00 320.00 Hz
653.36
1240 -
P2.4.17
Inching ramp
0.1
3200.0 s
1.0
1257 -
P2.4.18
Quick stop mode
0
1
-
0
1276 0 = Coasting
1 = Ramp
P2.4.19
Control options
0
65536
-
0
1084 -
P2.4.20
Modulator type
0
1
-
0
1516 0 = ASIC modulator
1 = Software Modulator 1
P2.4.21
Ramp; Skip S2
0
1
-
0
1900 -
P2.4.22
Reverse VW Phases
0
1
-
0
1062 -
P2.4.23
Overvoltage Ref Selection
0
2
-
1
1262 0 = High Voltage
1 = Nominal Voltage
AB296635287482en-000301 / DPD00903
104 | Danfoss A/S © 2023.02
Multi-purpose Control Application
VACON® NX All-in-One
Application Guide