2.7.50
Klixon Response
0
3
-
2
782
0 = No Action
1 = Warning, Warning
2 = Warning, Fault
3 = Fault, Fault
2.7.51
Ambient Temperature Re-
sponse
0
2
-
1
784
0 = No Action
1 = Warning
2 = Fault
2.7.52
Input Switch Response
0
2
-
0
785
0 = No Action
1 = Warning
2 = Fault
7.4.10 Autorestart Parameters (Control Panel: Menu M2 -> G2.8)
Table 83: Autorestart Parameters, G2.8
Index
Parameter
Min
Max
Unit Default
ID
Description
P2.8.1
Wait time
0.10 10.00
s
0.50
717 -
P2.8.2
Trial time
0.00 60.00
s
30.00
718 -
P2.8.3
Start function
0
2
-
0
719 0 = Ramp
1 = Flying start
2 = According to P2.4.6
P2.8.4
Number of tries after undervoltage trip
0
10
-
0
720 -
P2.8.5
Number of tries after overvoltage trip
0
10
-
0
721 -
P2.8.6
Number of tries after overcurrent trip
0
3
-
0
722 -
P2.8.7
Number of tries after 4 mA reference trip
0
10
-
0
723 -
P2.8.8
Number of tries after motor temperature fault trip
0
10
-
0
726 -
P2.8.9
Number of tries after external fault trip
0
10
-
0
725 -
P2.8.10
Number of tries after underload fault trip
0
10
-
0
738 -
7.4.11 Fieldbus Parameters (Control Panel: Menu M2 -> G2.9)
Table 84: Fieldbus Parameters, G2.9
Index
Parameter
Min
Max
Unit
Default
ID
Description
P2.9.1
Fieldbus min scale
0.00
320.00
Hz
0.00
850
-
P2.9.2
Fieldbus max scale
0.00
320.00
Hz
0.00
851
-
P2.9.3
Fieldbus process data out 1 selection
0
10000
-
1
852
-
AB296635287482en-000301 / DPD00903
118 | Danfoss A/S © 2023.02
Multi-purpose Control Application
VACON® NX All-in-One
Application Guide