Index
Parameter
Min Max
Unit Default ID
Description
4 = Used when running (no testing)
P2.4.6
Start function
0
2
-
0
505 0 = Ramp
1 = Flying start
2 = Conditional flying start
P2.4.7
Stop function
0
3
-
0
506 0 = Coasting
1 = Ramp
2 = Ramp+Run enable coast
3 = Coast+Run enable ramp
P2.4.8
DC braking current
0.00 I
L
A
0.7 x I
H
507 -
P2.4.9
DC braking time at stop
0.00 600.00 s
0.00
508 0 = DC brake is off at stop
P2.4.10 Frequency to start DC braking during
ramp stop
0.10 10.00
Hz
1.50
515 -
P2.4.11 DC braking time at start
0.00 600.00 s
0.00
516 0 = DC brake is off at start
P2.4.12 Flux brake
0
1
-
0
520 0 = Off
1 = On
P2.4.13 Flux braking current
0.00 I
L
A
I
H
519 -
8.4.6 Prohibit Frequency Parameters (Control Panel: Menu M2 -> G2.5)
Table 104: Prohibit Frequency Parameters, G2.5
Index
Parameter
Min
Max
Unit
Default
ID
Description
P2.5.1
Prohibit frequency range 1 low limit
-1.00
320.00
Hz
0.00
509
0 = Not used
P2.5.2
Prohibit frequency range 1 high limit
0.00
320.00
Hz
0.00
510
0 = Not used
P2.5.3
Prohibit frequency range 2 low limit
0.00
320.00
Hz
0.00
511
0 = Not used
P2.5.4
Prohibit frequency range 2 high limit
0.00
320.00
Hz
0.00
512
0 = Not used
P2.5.5
Prohibit frequency range 3 low limit
0.00
320.00
Hz
0.00
513
0 = Not used
P2.5.6
Prohibit frequency range 3 high limit
0.00
320.00
Hz
0.00
514
0 = Not used
P2.5.7
Prohibit acc./dec. ramp
0.1
10.0
x
1.0
518
-
8.4.7 Motor Control Parameters (Control Panel: Menu M2 ->G2.6)
Table 105: Motor Control Parameters, G2.6
Index
Parameter
Min
Max
Unit
Default
ID
Description
P2.6.1
(1)
Motor control mode
0
1
-
0
600
0 = Frequency control
AB296635287482en-000301 / DPD00903
144 | Danfoss A/S © 2023.02
Pump and Fan Control Application
VACON® NX All-in-One
Application Guide