10.77 (ID 319) DIN 2 Function
Location in the menu:
P2.2.1
(PID Control Application)
Use this parameter to select the function for the digital input signal.
This parameter has 14 selections. If digital input DIN 2 is not needed, set the parameter value to 0.
Table 117: Selections for Parameter ID 319
Selec-
tion
number
Selection name
Description
Notes
1
External fault, nor-
mally open
Contact closed: Fault is shown and
motor stopped when the input is ac-
tive
-
2
External fault, nor-
mally closed
Contact open: Fault is shown and
motor stopped when the input is not
active.
-
3
Run enable
Contact open, Start of motor disa-
bled.
-
Contact closed: Start of motor ena-
bled
-
4
Acceleration or de-
celeration time se-
lection
Contact open, Acceleration/Deceler-
ation time 1 selected
-
Contact closed: Acceleration/Decel-
eration time 2 selected
-
5
Closing contact
Force control place to I/O terminal
When the control place is forced to change, the values
of Start/Stop, Direction, and Reference valid in the re-
AB296635287482en-000301 / DPD00903 | 193
Danfoss A/S © 2023.02
Parameter Descriptions
VACON® NX All-in-One
Application Guide