•
•
1.0
0
20 mA
4 mA
10 mA
0.5
0 mA
12 mA
ID311 =
100%
ID311 =
200%
ID311=
50%
ID310 = 1
ID310 = 0
e
3
0
b
h
0
3
3
.1
0
A
B
Illustration 40: Analog Output Scaling
A
Analog output current
B
Maximum value of signal selected with ID 307
Use this formula to calculate the values:
OutputSignal = Signal
∗
Analogue Output Scale %
100 %
10.72 (ID 312) Digital Output Function
Location in the menu:
P2.3.7
(Standard Application, Local/Remote Control Application, Multi-Step Speed Control Application, PID Control Application)
P2.3.1.2
(Multi-Purpose Control Application)
Use this parameter to select the function for the digital output signal.
Setting value
Signal content
0 = Not used
Out of operation.
1 = Ready
The AC drive is ready to operate.
2 = Run
The AC drive operates (motor is running).
3 = Fault
A fault trip has occurred.
4 = Fault inverted
A fault trip not occurred
5 = AC drive overheat warning
The heat sink temperature e70 °C.
6 = External fault or warning
Fault or warning depending on parameter ID 701.
7 = Reference fault or warning
Fault or warning depending on parameter ID 700 - if analog reference is 4–20 mA
and signal is <4 mA.
8 = Warning
Always if a warning exists.
9 = Reversed
The reverse command has been selected.
10 = Preset speed
(1)
The preset speed has been selected with digital input.
10 = Jogging speed
(2)
The jogging speed has been selected with digital input.
11 = At speed
The output frequency has reached the set reference.
AB296635287482en-000301 / DPD00903
190 | Danfoss A/S © 2023.02
Parameter Descriptions
VACON® NX All-in-One
Application Guide
Summary of Contents for VACON NX
Page 1: ...Application Guide VACON NX All in One drives danfoss com...
Page 2: ......