InteliDrive Lite - 1.2.1 Global guide
57
Speed Sel3
If the input is active, the Engine params: BI Speed Sel3 setpoint may give the engine speed value for Speed
request to an ECU engine. The Speed Request value may also depend on the conditions which are described in
the chapter below.
Note:
Engine params: RetToSpeedAdj = DISABLED, Speed request is adjusted by BI Speed Sel1, 2, 3 edge
(button press), i.e. input can be opened and Speed request stay constant.
Note:
Engine params: RetToSpeedAdj = ENABLED, Speed request is adjusted by BI Speed Sel1, 2, 3 level
(switch), i.e. when input is opened Speed request go back to Engine params: ECU SpeedAdj level.
Note:
SpeedSel1, 2,.3 binary inputs are active only when Regulator: LAI SpdSelect = OFF.
Note:
When more binary inputs are active at the same time, e.g. all binary inputs: ‘Speed Sel1’, ‘Speed Sel2’,
‘Speed Sel3’ then requested speed is given by Engine params: BI Speed Sel 1 (lowest index) setpoint.
Lang selection
Switch display texts between two languages.
Conveyor
Initial condition: Running engine.
Rising edge BI Conveyor activates BO Horn for Engine params: Conveyor horn. And after horn is over activates
the BO Conveyor.
The second rising edge of BI Conveyor opens the BO Conveyor. BO Conveyor is deactivated in case of Sd
protection.
LoadRequest2
Active input switches the Load limit request to Load limit: LoadRequest2 setpoint.
R Reg Disable
Active input disables the Regulator PI loop and switches analog output to constant Regulator: Reg bias.
Clear DayCons
DayCons is the counter which cumulates the instantanous consumption coming from ECU. It shows the total
consumption since the counter reset. Counte reset happen at the midnight of the controller clocks. LBI Clear
DayCons resets the counter DayCons.
Note:
The function works when the controller is connected to an ECU or in other case is consumption counted
from the changes of analog input value Fuel rate and setpoint Engine params: FuelTankVolume.