InteliDrive Lite - 1.2.1 Global guide
62
Horn
The output closes if:
any warning or shutdown comes up or
the engine malfunctions
The output opens if:
FAULT RESET is pressed or
HORN RESET is pressed or
Max time of LBO HORN is exceeded (Horn timeout)
The output closes again if a new fault comes up.
Ready
The output is closed if following conditions are fulfilled:
Engine is not running and
No Shut down or Slow stop alarm is active
Controller is not in OFF mode
Ready to load
The output is closed if engine is running and no alarm is active - it is possible to close load. The output opens
when Wrn Underspeed protection is active and during cooling state.
Running
Output closes if the engine is in Running state.
Cooling
The output closes when engine is in Cooling state.
Fault Reset
One second pulse as echo for panel Fault reset button.
ChrgAlternFail
Output closes if engine is running and D+ input not energized.
The output opens, if
alarm is not active and
FAULT RESET is pressed
Note:
Threshold level for D+ input is 80% supply voltage.
Stop failed
Output closes when the engine has to be stopped, but speed or oil pressure is detected. This protection goes
active 60 s after stop command.
The output opens, if