![ComAp ID-FLX-Lite-PC Global Manual Download Page 141](http://html1.mh-extra.com/html/comap/id-flx-lite-pc/id-flx-lite-pc_global-manual_2638902141.webp)
InteliDrive Lite - 1.2.1 Global guide
141
Setpoint group
Engine params 2
Related FW
1.2.1
Range [units]
1 - MaxSpeedLim [1/s]
Default value
50 1/s
Force value
Step
1 1/s
Comm object
10148
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Any Speed request change is done via this Ramp function. The Ramp via Binary SpeedUp and SpeedDown
inputs is dual rate, see below.
The Binary inputs SpeedUp and SpeedDown ramp function is for the 0.6s constant 5RPM/s. Does not
depend on Engine params 2: Speed Ramp setting. This enables fine setting of Engine speed to specific
value e.g. 1500 RPM.
Speed Ramp