InteliDrive Lite - 1.2.1 Global guide
79
7.1.4 Shut down (Sd)
When the shutdown alarm comes up, InteliDrive IPC opens all outputs e.g. FUEL SOLENOID, STARTER and
PRESTART to stop the engine immediately. Alarm outputs and common shutdown output are closed. Active or
not reset protection disables start.
Note:
Engine running only alarms are activated after
Engine protect
: Eng prot del, after the engine RPM >
Engine params
: Starting RPM during the engine starting procedure.
Note:
If LBI Sprinkler is active engine does not react on shutdown protection only for Emergency stop and
Overspeed protection.
7.1.5 List of possible alarms
Events
specification
Protection
type
Information
on binary
output
available
Description
Wrn Oil Press
WRN
YES
Oil pressure is smaller than Wrn Oil
press setpoint.
Sd Oil Press
SD
YES
Oil pressure is smaller than Sd Oil
press setpoint.
Sd NotOilPress
SD
YES
No information about the oil pressure
from the binary oil pressure sensor.
Wrn Engine Temp
WRN
YES
Water temperature is greater than Wrn
Water temp setpoint.
Sd Engine Temp
SD
YES
Water temperature is greater than Sd
Water temp setpoint.
Wrn Fuel Level
WRN
YES
Fuel level is smaller than Wrn Fuel
Level setpoint.
Sd Fuel Level
SD
YES
Fuel level is smaller than Sd Fuel
Level setpoint.
Ubat
WRN
YES
Battery voltage is out of limits given
by Batt overvolt and Batt undervolt
setpoints.
Wrn AIN
WRN
YES
Warning alarm configurable on the
input of the controller
Sd AIN
SD
YES
Shutdown alarm configurable on the
input of the controller.
Wrn AIO
WRN
YES
Warning alarm configurable on the
input of plug-in.
Sd AIO
SD
YES
Shutdown alarm configurable on the
input of plug-in.
Binary input
Configurable
YES
Configurable Warning/Shutdown
alarms on the inputs of InteliDrive IPC