InteliDrive Lite - 1.2.1 Global guide
58
Clear TripCons
TripCon is the counter which cumulates the instantanous consumption coming from ECU. It shows the total
consuption since last reset by LBI Clear TripCon. This LBI resets the counter TripCons.
Note:
The function works when the controller is connected to an ECU or in other case is consumption counted
from the changes of analog input value Fuel rate and setpoint Engine params: FuelTankVolume.
Flow Switch
FlowSwitch is protection to stop the engine in case the water not flow. Function is active in MAN and AUT
mode. Engine is switched to Cooling state when FlowSwitch is not closed within Engine protect: Flow
SwitchDel after running (Ready to load) engine state activation. Function stops the engine in AUT mode with
FlowSwitch indication in Alarm list and stays in AUT mode after Fault reset.
Alarm list and History indication = "Cd Flow Switch" (CoolDown is third engine protection type in InteliDrive
Lite).
Machine state stays in Cooling even the LBI FLow Switch is activated again during Cooling period.
Prot Test
When the new LBI Protection Test is activated (by rising edge), all Sd alarms are for 90 s blocked. The
exception is LBI Emergency stop and Overspeed protection.
TimerInhibit
Created new LBI TimerInhibit which is intended to preventing engine start by Timer 1 and Timer 2 or stop the
running engine during running Timer1 and Timer 2. The possibility of using:
The engine isn't started by Timer 1/2 if LBI TimerInhibit is active at a time of timer start.
The engine is stopped during running Timer 1/2 when LBI TimerInhibit is activated for time set in setpoint
TimerInhibitDel (group: Date/Time).
The engine isn't stopped during running Timer 1/2 when LBI TimerInhibit is activated for shorter time set in
setpoint TimerInhibitDel (group: Date/Time).