InteliDrive Lite - 1.2.1 Global guide
200
Setpoint group
AIO module
Related FW
1.2.1
Range [units]
0 - 180 [s]
Default value
5 s
Force value
Step
1 s
Comm object
13659
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Delay for IL-NT-AIO plug-in card Analog input 2 alarm.
Note:
Plug-in analog inputs protection alarms can be configured following way
Configuration
Protection
Under limit
Protection is activated only when measured value is under measured
level.
Over limit
Protection is activated only when measured value is over measured level.
Undfls
Level 2 protection is activated by sensor fail too.
Ovfls
Level 2 protection is activated by sensor fail too.
AnlInAIO2 del
Setpoint group
AIO module
Related FW
1.2.1
Range [units]
0 - 180 [s]
Default value
5 s
Force value
Step
1 s
Comm object
13660
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Delay for IL-NT-AIO plug-in card Analog input 3 alarm.
Note:
Plug-in analog inputs protection alarms can be configured following way
Configuration
Protection
Under limit
Protection is activated only when measured value is under measured
level.
Over limit
Protection is activated only when measured value is over measured level.
Undfls
Level 2 protection is activated by sensor fail too.
Ovfls
Level 2 protection is activated by sensor fail too.
AnlInAIO3 del