InteliDrive Lite - 1.2.1 Global guide
153
Setpoint group
Load limit
Related FW
1.2.1
Range [units]
-200 - +200 [%]
Default value
10 %
Force value
Step
0.1 %
Comm object
11857
Related applications
Config level
Standard
Setpoint visibility
Always
Description
This is setpoint is giving Load limit gain factor.
Load Gain
Setpoint group
Load limit
Related FW
1.2.1
Range [units]
0 - +100 [%]
Default value
10 %
Force value
Step
0.1 %
Comm object
11858
Related applications
Config level
Standard
Setpoint visibility
Always
Description
This setpoint is giving Load limit integration factor.
Load Integral
Setpoint group
Load limit
Related FW
1.2.1
Range [units]
[-]
Default value
RPM
Force value
Step
[-]
Comm object
11859
Related applications
Config level
Standard
Setpoint visibility
Always
Description
This setpoint is for Load limit comparetor with hysteresis analog input selection. Source can be adjusted
from controller RPM pick-up, ECU, analog inputs or from extension module inputs.
Load CMP Input