97
9.8.1 Engine RPM Idle - Nominal switching
Binary input Nominal/Idle switchs RPM to
Engine params
:
Idle speed
when closed (in MAN mode only).
Opened input ramps to
Engine params
:
ECU SpeedAdj
. No RPM control is active in engine Idle state.
9.8.2 Engine RPM two/three levels switching
Continuing example above …. closed BI Speed Sel1, 2, 3 ramps the Engine RPM to the selected setpoint level.
… i.e. switched/ramped to another three levels.
Note:
Necessary condition:
Regulator
: LAI SpeedReq = OFF and controller MAN mode.
9.8.3 Engine RPM by Up/Down buttons settings
RPM adjusted in examples above can be changed by BI Speed Up / Speed Down when the Engine params:
RetToSpeedAdj = DISABLED.
Note:
Necessary condition:
Regulator
: LAI SpeedReq = OFF and controller MAN mode.
9.8.4 Engine RPM continuous change (using potentiometer)
Adjust
Regulator
:
LAI SpeedReq
= AI1-9 … to corresponding controller or extension module analog input.
Configure this Analog input - sensor characteristic in RPM or Percentage (expected potentiometer resistance
2,5kOhm in example below).
Engine params
: Speed ramp setpoint is active.