Setpoint group
Engine params 2
Related FW
1.2.1
Range [units]
MinSpeedLim - MaxSpeedLim [RPM]
Default value
1250 RPM
Force value
Step
1 RPM
Comm object
10099
Related applications
Config level
Standard
Setpoint visibility
Always
Description
The setpoint presets the required engine speed during the ‘Speed Sel 1’ binary input is active. Function
depends on RetToSpeedAdj setting.
BI Speed Sel 1
Setpoint group
Engine params 2
Related FW
1.2.1
Range [units]
MinSpeedLim - MaxSpeedLim [RPM]
Default value
1300 RPM
Force value
Step
1 RPM
Comm object
10523
Related applications
Config level
Standard
Setpoint visibility
Always
Description
The setpoint presets the required engine speed during the ‘Speed Sel 2’ binary input is active. Function
depends on RetToSpeedAdj setting.
BI Speed Sel 2
Setpoint group
Engine params 2
Related FW
1.2.1
Range [units]
MinSpeedLim - MaxSpeedLim [RPM]
Default value
1450 RPM
Force value
Step
1 RPM
Comm object
10524
Related applications
Config level
Standard
Setpoint visibility
Always
Description
The setpoint presets the required engine speed during the ‘Speed Sel 3’ binary input is active. Function
depends on RetToSpeedAdj setting.
Note:
When none of the binary inputs: ‘Speed Sel1’, ‘Speed Sel2’ and ‘Speed Sel3’, ‘Speed Up’ and
‘Speed Down’ has not been configured then engine speed is given by the ‘Engine params 2: ECU
SpeedAdj‘ setpoint.
BI Speed Sel 3