InteliDrive Lite - 1.2.1 Global guide
133
Setpoint group
Engine params
Related FW
1.2.1
Range [units]
0 - 240 [s]
Default value
10 s
Force value
Step
1 s
Comm object
9815
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Under normal conditions the engine must certainly stop within this period. The period starts by issuing stop
command.
Note:
Stop of engine is detected when all following conditions are met: RPM <2, Oil pressure <
StartingPOil and D+ input isn’t active.
Note:
Stop fail is detected if there is difference between those conditions.
Note:
In case when stop time period is lower than "stop engine detected" + 10 s, stop time period is
extended to this value due to safety reason. (stop engine detected = RPM<2, OilP not detected, D+ not
active)
Stop time
Setpoint group
Engine params
Related FW
1.2.1
Range [units]
0 - 1000 [min]
Default value
0 min
Force value
Step
1 min
Comm object
11837
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Automatic engine stop in MAN mode, no function in AUT mode. Start engine in MAN mode by START
button. Engine stops itself after Running Timer expires. Engine keeps running when Running Timer = 0.
Running timer
10.1.8 Group: Engine params 2
Note:
Following setpoints are available from LiteEdit/InteliMonitor only.