InteliDrive Lite - 1.2.1 Global guide
119
Setpoint group
Basic Settings 2
Related FW
1.2.1
Range [units]
[-]
Default value
AUTO
Force value
Step
[-]
Comm object
13345
Related applications
Config level
Standard
Setpoint visibility
Always
Description
This setpoint is used for adjustment of RunHours source of the engine.
ECU: RunHours are all the time read from ECU.
INTERNAL: RunHours are counted from the inner counter of the controller.
AUTO: If is coming from ECU rational value higher than 0, then the RunHours are taken from ECU, in
second case are displayed internal hours from controller. Default state.
IMPORTANT: Some types of ECUs reset RunHours counter to 0, if the supply was
disconnected.
RunHoursSource
Setpoint group
Basic Settings 2
Related FW
1.2.1
Range [units]
[-]
Default value
AIN2
Force value
Step
[-]
Comm object
13346
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Change the display of the main Measurment screen.
SHOW AIN: Instead of timers are on the left side of the screen displayed values of analog inputs AIN6 and
AIN7
Main Screen 1