![ComAp ID-FLX-Lite-PC Global Manual Download Page 168](http://html1.mh-extra.com/html/comap/id-flx-lite-pc/id-flx-lite-pc_global-manual_2638902168.webp)
InteliDrive Lite - 1.2.1 Global guide
168
Setpoint group
Engine protect
Related FW
1.2.1
Range [units]
0 - 10000 [U17]
Default value
10 U17
Force value
Step
1 U17
Comm object
13357
Related applications
Config level
Standard
Setpoint visibility
Always
Description
High ShutDown limit level for AIN5
Setpoint name depends on setting of AIN5 (maximum length is 14 characters).
AIN5 HighSd
Setpoint group
Engine protect
Related FW
1.2.1
Range [units]
0 - 3600 [s]
Default value
10 s
Force value
Step
1 s
Comm object
13358
Related applications
Config level
Standard
Setpoint visibility
Always
Description
High level protection delay for Wrn and Sd of AIN5
Setpoint name depends on setting of AIN5 (maximum length is 14 characters).
Note:
Analog input 5 is fully configurable and it is voltage type of input with range 0-40V
AIN5 HighDel
Setpoint group
Engine protect
Related FW
1.2.1
Range [units]
[-]
Default value
ENABLED
Force value
Step
[-]
Comm object
14658
Related applications
Config level
Standard
Setpoint visibility
Always
Description
The setting DISABLED disables all configured protections, except Overspeed and Emergency Stop. It is
indicated in the alarm list by warning Prot AIN6 dis. Each configuration change is recorded in history,
records: Prot AIN6 dis and Prot AIN6 ena.
Setpoint name depends on setting of AIN6 (maximum length is 14 characters).
AIN6 prot