![ComAp ID-FLX-Lite-PC Global Manual Download Page 64](http://html1.mh-extra.com/html/comap/id-flx-lite-pc/id-flx-lite-pc_global-manual_2638902064.webp)
InteliDrive Lite - 1.2.1 Global guide
64
Common Sd
Output closes when any shutdown alarm appears.
The output opens, if
No Sd alarm is active and
FAULT RESET is pressed
Common Cd
Output closes when any cooldown alarm appears.
The output opens, if
No Cd alarm is active and
FAULT RESET is pressed
Common Fls
Output closes when any sensor fail alarm appears.
The output opens, if
No warning alarm is active and
FAULT RESET is pressed
Sd Oil Press
Output closes if the oil pressure shutdown alarm activates.
The output opens, if
alarm is not active and
FAULT RESET is pressed
Wrn Oil Press
Output closes if the oil pressure warning alarm activates.
The output opens, if
alarm is not active and
FAULT RESET is pressed
Sd Engine Temp
Output closes if the water temperature shutdown alarm activates.
The output opens, if
alarm is not active and
FAULT RESET is pressed
Wrn Engine Temp
Output closes if the water temperature warning alarm activates.
The output opens, if