![ComAp ID-FLX-Lite-PC Global Manual Download Page 37](http://html1.mh-extra.com/html/comap/id-flx-lite-pc/id-flx-lite-pc_global-manual_2638902037.webp)
InteliDrive Lite - 1.2.1 Global guide
37
Note:
The FTDI driver is installed together with LiteEdit.
Note:
When the USB cable from the controller is plugged-in first time into different USB ports on the PC
including USB hubs, it can be recognized as new hardware and the drivers are installed again with different
number of the virtual serial port.
IMPORTANT: Use shielded USB cable only! (ComAp order code: USB-LINK CABLE 1.8m)
4.6.4 IB-Lite
IB-Lite is a optional plug-in card with Ethernet 10/100 Mbps interface in RJ45 connector. The card is internally
connected to both COM1 and COM2 serial channels and provides an interface for connecting a PC with LiteEdit
or InteliMonitor through Ethernet network, for sending active e-mails and for integration of the controllers into a
building management (Modbus/TCP protocol).
This card also enables to monitor and control the consumption engines over web browser from any location with
internet access using appropriate security measures.
Note:
Use Ethernet UTP cable with RJ45 connector for connection of the module into your ethernet network.
The module can be also connected directly to a PC using cross-wired UTP cable.
Note:
The module requires configuration settings before usage. See IB-Lite 1.x Reference Guide.