![ComAp ID-FLX-Lite-PC Global Manual Download Page 130](http://html1.mh-extra.com/html/comap/id-flx-lite-pc/id-flx-lite-pc_global-manual_2638902130.webp)
InteliDrive Lite - 1.2.1 Global guide
130
Setpoint group
Engine params
Related FW
1.2.1
Range [units]
1 - 60 [s]
Default value
10 s
Force value
Step
1 s
Comm object
8257
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Pause between crank (engine start) attempts.
CrnkFail pause
Setpoint group
Engine params
Related FW
1.2.1
Range [units]
1 - 10 [-]
Default value
3
Force value
Step
1
Comm object
8255
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Maximum number of crank (engine start) attempts.
Crank attempts
Setpoint group
Engine params
Related FW
1.2.1
Range [units]
0 - 60 [s]
Default value
0 s
Force value
Step
1 s
Comm object
14687
Related applications
Config level
Standard
Setpoint visibility
Always
Description
The condition oil pressure >
Starting POil
is considered fulfilled after
Start POil Del
.
Note:
This parameter can be used for complete disabling of oil pressure engine running condition.
Therefore, this adjustment must be done very carefully.
Start POil Del