InteliDrive Lite - 1.2.1 Global guide
56
StopButton
Binary input has the same function as Stop button on the InteliDrive IPC front panel. It is active in MAN mode
only.
FaultResButton
Binary input has the same function as Fault reset button on the InteliDrive IPC front panel.
HornResButton
Binary input has the same function as Horn reset button on the InteliDrive IPC front panel.
Nominal/Idle
Input works in MAN mode only switching between running states Nominal/Idle. Active Nominal/Idle input
activates binary output Idle/Nominal and sends Speed request = Engine params: Idle speed and/or active
(binary) IDLE command to the ECU (e.g. to Volvo EMS).
Eng.state
Sped request in MAN mode
Sped request in AUT mode
Idle
Engine params: Idle speed
Engine params: Idle speed
Running
Engine params: ECU SpeedAdj
anything within
Engine params: MinSpeedLim
Engine params: MaxSpeedLim
Active input opens the binary output Ready to Load during the engine running state. Ready to Load can be
closed back (if other conditions are fulfilled – see the Ready to Load binary output description) if Nominal/Idle is
opened.
Speed Up
If the input is active, the Speed Request may increase the engine speed value. The Speed Request value may
also depend on the conditions which are described in the chapter below.
Speed Down
If the input is active, the Speed Request may decrease the engine speed value. The Speed Request value may
also depend on the conditions which are described in the chapter below.
Note:
Speed Up/Down binary inputs are active only when Regulator: LAI SpdSelect = OFF.
Speed Sel1
If the input is active, the Speed request = Engine params: BI Speed Sel1 setpoint. The function is affected by
Engine params: RetToSpeedAdj.
Speed Sel2
If the input is active, the Engine params: BI Speed Sel2 setpoint may give the engine speed value for Speed
request to an ECU engine. The Speed Request value may also depend on the conditions which are described in
the chapter below.