InteliDrive Lite - 1.2.1 Global guide
201
Setpoint group
AIO module
Related FW
1.2.1
Range [units]
0 - 180 [s]
Default value
5 s
Force value
Step
1 s
Comm object
13661
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Delay for IL-NT-AIO plug-in card Analog input 4 alarm.
Note:
Plug-in analog inputs protection alarms can be configured following way
Configuration
Protection
Under limit
Protection is activated only when measured value is under measured
level.
Over limit
Protection is activated only when measured value is over measured level.
Undfls
Level 2 protection is activated by sensor fail too.
Ovfls
Level 2 protection is activated by sensor fail too.
AnlInAIO4 del
10.1.18 Group: SMS_E-Mail
Note:
If a cellular network modem and/or internet bridge is connected to the controller, the controller can send
SMS messages and/or emails in the moment when a new alarm appears in the Alarm list. The message will
contain a copy of the Alarm list.To enable this function, you should select with setpoints Yel Alarm Msg and
Red Alarm Msg, which levels of alarms shall be announced (red/yellow/both) and also enter valid cellular
network phone number and/or e-mail address to the setpoints TelNo/Addr Ch1 and TelNo/Addr Ch2. It is
possible to put either number or e-mail to both setpoints.
Note:
An internet module must be available for sending of e-mails. Similarly, a cellular network modem is
necessary for sending of SMS.
Note:
There are 5 attempts for any active call (SMS/E-Mail). Timeout for connection is 90 sec and after 120 sec
controller starts the next attempt. During the time the IL-NT-GPRS is trying to send an active call type,
incoming calls are blocked.