![ComAp ID-FLX-Lite-PC Global Manual Download Page 93](http://html1.mh-extra.com/html/comap/id-flx-lite-pc/id-flx-lite-pc_global-manual_2638902093.webp)
InteliDrive Lite - 1.2.1 Global guide
93
State
Condition of the
transition
Action
Next state
elapsed, 1st attempt
FUEL SOLENOID off
STOP SOLENOID on
CrankFail pause timer
started
MaxCrank time
elapsed, last attempt
STARTER off
PRESTART off
Shutdown (Start fail)
Crank
pause
1
CrankFail pause
elapsed
STARTER on
FUEL SOLENOID on
2
STOP SOLENOID off
MaxCrank time counter
started
Cranking
Starting
1
BI: Nominal/Idle is
active
FUEL SOLENOID on
2
STOP SOLENOID off
READY TO LOAD off
Idle
RPM = 0 or any other
shutdown condition
FUEL SOLENOID off
STOP SOLENOID on
Shutdown
60 sec. Elapsed
FUEL SOLENOID off
STOP SOLENOID on
Shutdown (Start fail)
Idle
1
BI: Nominal/Idle
is
active
Idle timer Elapsed
FUEL SOLENOID on
2
STOP SOLENOID off
READY TO LOAD off
Running
RPM = 0 or any other
shutdown condition
FUEL SOLENOID off
STOP SOLENOID on
Shutdown
Running
Stop request
READY TO LOAD off
Cooling time timer started
Cooling
BI: Nominal/Idle
is
active
FUEL SOLENOID on
STOP SOLENOID off
READY TO LOAD off
Running
RPM = 0 or any other
shutdown condition
FUEL SOLENOID off
STOP SOLENOID on
READY TO LOAD off
Shutdown
Cooling
Cooling time elapsed
FUEL SOLENOID off
STOP SOLENOID on
Stop
RPM = 0 or any other
shutdown condition
FUEL SOLENOID off
STOP SOLENOID on
Shutdown