![ComAp ID-FLX-Lite-PC Global Manual Download Page 162](http://html1.mh-extra.com/html/comap/id-flx-lite-pc/id-flx-lite-pc_global-manual_2638902162.webp)
InteliDrive Lite - 1.2.1 Global guide
162
Setpoint group
Engine protect
Related FW
1.2.1
Range [units]
[-]
Default value
ENABLED
Force value
Step
[-]
Comm object
14656
Related applications
Config level
Standard
Setpoint visibility
Always
Description
The setting DISABLED disables all configured protections, except Overspeed and Emergency Stop. It is
indicated in the alarm list by warning Prot AIN4 dis. Each configuration change is recorded in history,
records: Prot AIN4 dis and Prot AIN4 ena.
Setpoint name depends on setting of AIN4 (maximum length is 14 characters).
AIN4 prot
Setpoint group
Engine protect
Related FW
1.2.1
Range [units]
0 - 10000 [U16]
Default value
20 U16
Force value
Step
1 U16
Comm object
9271
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Warning limit level for AIN4
Setpoint name depends on setting of AIN4 (maximum length is 14 characters).
AIN4 Wrn
Setpoint group
Engine protect
Related FW
1.2.1
Range [units]
0 - 10000 [U16]
Default value
10 U16
Force value
Step
1 U16
Comm object
9272
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Shutdown limit level for AIN4
Setpoint name depends on setting of AIN4 (maximum length is 14 characters).
AIN4 Sd