InteliDrive Lite - 1.2.1 Global guide
155
Setpoint group
Engine protect
Related FW
1.2.1
Range [units]
Starting RPM - 100 [%]
Default value
25 %
Force value
Step
1 % of nominal RPM
Comm object
8260
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Limit for Warning Underspeed protection. Active protection is indicated as “Wrn Underspeed” in Alarm list.
Under speed Warning protection is inactive 5s after RPM is over
Engine params
: Starting RPM and during
the Idle time.
The “Ready to load” output is deactivated when Wrn underspeed protection is active and needs the Fault
reset for activation after RPM is over Underspeed limit.
Underspeed
Setpoint group
Engine protect
Related FW
1.2.1
Range [units]
0 - 600 [s]
Default value
30 s
Force value
Step
1 s
Comm object
12620
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Engine is switched to Cooling state when Binary input FlowSwitch is not closed within Flow SwitchDel after
„Running“ (Ready to load) engine state activation.
Flow SwitchDel