InteliDrive Lite - 1.2.1 Global guide
63
alarm is not active and
FAULT RESET is pressed
Overspeed
Output closes if the engine over speed alarm activates.
The output opens, if
alarm is not active and
FAULT RESET is pressed
Underspeed
Output closes if the engine “Sd Underspeed” alarm activates i.e. when RPM is below the Engine params:
Starting RPM limit.
The output opens, if
alarm is not active and
FAULT RESET is pressed
Stop failed
Output closes when the engine has to be stopped, but speed or oil pressure is detected. This protection goes
active 60 s after stop command.
The output opens, if
alarm is not active and
FAULT RESET is pressed
Battery flat
Output closes when InteliDrive IPC performs reset during start procedure (probably due to weak battery).
The output opens, if
Alarm is not active and
FAULT RESET is pressed
V batt failed
Output closes when battery over/under voltage warning appears.
The output opens, if
alarm is not active and
FAULT RESET is pressed
Common Wrn
Output closes when any warning alarm appears.
The output opens, if
No warning alarm is active and
FAULT RESET is pressed