New setpoint group ATT Settings
Created new setpoint group ATT Settings what includes two parameters:
Regen Inhibit – set ECU value Aftertreatment Regeneration Inhibit Switch (SPN 3695). There can be
set:
OFF – automatic filter regeneration is enabled - SPN 3695 = 00b
ON – automatic filter regeneration is inhibited - SPN 3695 = 01b
BIN – value is set by LBI Regen Inhibit
Transmitted value is set by actual level of parameter ON/OFF or by level of LBI.
Regen Force – set ECU value Aftertreatment Regeneration Force Switch (SPN 3696). There can be
set:
OFF – automatic filter regeneration is enabled
ON – automatic filter regeneration is inhibited
BIN – value is set by LBI Regen Force
Transmitted value is activated for 5 sec. by rising edge of parameter change OFF to ON or LBI.
Support of proprietary John Deere CAN message
Created proprietary John Deere CAN message DPF Lockout – PGN 61184, transmitted value:
ON = F2 31 FF FF CF FF FF FF
OFF = F2 31 FF FF DF FF FF FF
Value is OFF if there isn’t configured LBI ATT Lockout1 neither ATT Lockout2 or all configured LBI ATT
Lockout are active.
Value is ON if min. one of configured LBI ATT Lockout is inactive.
New LBO for all FT4 icons
Created new LBO what reflect all FT4 icons: DPF Inhibit, DPF Lamp, DPF Hest Lamp, DEF Level,
Malfunction, Red Lamp Icon, Wrn Lamp Icon.