Check ground connection from pick-up to controllers, eventually disconnect ground connection to one of
them
Galvanic separate InteliDrive IPC RPM input using ComAp separation transformer RPM-ISO (1:1)
Use separate pick-up for Speed governor and InteliDrive IPC
Note:
If RPM > 2 then the controller is in the state Not ready and the engine will not be allowed to start.
4.1.2 Analog inputs
On the InteliDrive IPC controller nine analog inputs are available. See the two tables here bellow with specific
characteristics.
All properties mentioned here can be modified by LiteEdit PC tool only, in the window Modify
Table of controller analog inputs
Input
Range
Default use
Configurability of default use
AIN1
0 - 2,4 kW
Oil pressure
NO
AIN2
0 - 2,4 kW
Engine temperature
YES
AIN3
0 - 2,4 kW
Fuel level
YES
AIN4
0 - 40 V
PumpSuction
YES
AIN5
0 - 40 V
PumpDischarge
YES
AIN6
0 - 10 V
PumpFlow
YES
Note:
The nominal range of Analog inputs measuring resistivity is 0- 2,4 kOhm, nevertheless the input is able to
measure up to 15 kOhm, but with lower precision.
Note:
When Engine Control Unit is connected, it is possible to read InteliDrive IPC Analog inputs values AIN1,
2, 3 from CAN bus (J1939).