![ComAp ID-FLX-Lite-PC Global Manual Download Page 132](http://html1.mh-extra.com/html/comap/id-flx-lite-pc/id-flx-lite-pc_global-manual_2638902132.webp)
InteliDrive Lite - 1.2.1 Global guide
132
Setpoint group
Engine params
Related FW
1.2.1
Range [units]
[-]
Default value
IDLE
Force value
Step
[-]
Comm object
10046
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Selects the function of the Binary output IDLE/NOMINAL during engine Cooling state
IDLE: Cooling is executed at Idle speed.
NOMINAL: Cooling is executed at Nominal speed. Default state.
Note:
Binary output IDLE/NOMINAL must be configured and connected to speed governor. Engine Idle
speed must be adjusted on speed governor.
Cooling speed
Setpoint group
Engine params
Related FW
1.2.1
Range [units]
0 - 3600 [s]
Default value
30 s
Force value
Step
1 s
Comm object
8258
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Run time of the unloaded engine to cool the engine before stop.
Cooling time