![ComAp ID-FLX-Lite-PC Global Manual Download Page 165](http://html1.mh-extra.com/html/comap/id-flx-lite-pc/id-flx-lite-pc_global-manual_2638902165.webp)
InteliDrive Lite - 1.2.1 Global guide
165
Setpoint group
Engine protect
Related FW
1.2.1
Range [units]
0 - 3600 [s]
Default value
10 s
Force value
Step
1 s
Comm object
13370
Related applications
Config level
Standard
Setpoint visibility
Always
Description
High level protection delay for Wrn and Sd of AIN4
Setpoint name depends on setting of AIN4 (maximum length is 14 characters).
Note:
Analog input 4 is fully configurable and it is voltage type of input with range 0-40V
AIN4 HighDel
Setpoint group
Engine protect
Related FW
1.2.1
Range [units]
[-]
Default value
ENABLED
Force value
Step
[-]
Comm object
14657
Related applications
Config level
Standard
Setpoint visibility
Always
Description
The setting DISABLED disables all configured protections, except Overspeed and Emergency Stop. It is
indicated in the alarm list by warning Prot AIN5 dis. Each configuration change is recorded in history,
records: Prot AIN5 dis and Prot AIN5 ena.
Setpoint name depends on setting of AIN5 (maximum length is 14 characters).
AIN5 prot
Setpoint group
Engine protect
Related FW
1.2.1
Range [units]
0 - 10000 [U17]
Default value
20 U17
Force value
Step
1 U17
Comm object
9274
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Warning limit level for AIN5
Setpoint name depends on setting of AIN5 (maximum length is 14 characters).
AIN5 Wrn