![ComAp ID-FLX-Lite-PC Global Manual Download Page 142](http://html1.mh-extra.com/html/comap/id-flx-lite-pc/id-flx-lite-pc_global-manual_2638902142.webp)
InteliDrive Lite - 1.2.1 Global guide
142
Setpoint group
Engine params 2
Related FW
1.2.1
Range [units]
0 - 3000 [RPM]
Default value
0 RPM
Force value
Step
1 RPM
Comm object
11125
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Limit for Speed Request transformation from RPM to % range for ECU engines using % format. See
practical example below.
Practical example:
If ECU is configured, then on one of the measurement screen you can see two lines SpeedReq Abs and
SpeedReq Rel.
In default setting:
0RPM = 0%
800RPM = 33.3%
2400RPM = 100%
Different setting:
800RPM = 0%
1200RPM = 33.3%
2400RPM = 100%
It is possible easily configure own output curve and use it for analog output Speed Request.
0%ofSpeedReq
Setpoint group
Engine params 2
Related FW
1.2.1
Range [units]
0 - 4000 [RPM]
Default value
2400 RPM
Force value
Step
1 RPM
Comm object
11126
Related applications
Config level
Standard
Setpoint visibility
Always
Description
Limit for Speed Request transformation from RPM to % range for ECU engines using % format.
100%ofSpeedReq