InteliDrive Lite - 1.2.1 Global guide
65
alarm is not active and
FAULT RESET is pressed
Sd FuelLevel
Output closes if the Fuel level shutdown alarm activates.
The output opens, if
alarm is not active and
FAULT RESET is pressed
Wrn FuelLevel
Output closes if the Fuel level warning alarm activates.
The output opens, if
alarm is not active and
FAULT RESET is pressed
OFF mode
The output is closed, if OFF mode is selected.
MAN mode
The output is closed, if MAN mode is selected.
AUT mode
The output is closed, if AUT mode is selected.
ServiceTime
Output closes if the ServiceTime alarm activates. Service time is adjusted by setpoint Engine protect:
NextServTime.
The output opens, if
alarm is not active and
FAULT RESET is pressed
DEF Tank Level
Output closes if the value DEF Tank Level drops under 10%, this level is adjustable in Engine protect: DEF
Level Min.
Outup opens if the value DEF Tank Level exceeds 90%. This upper limit is adjusted in Engine protect: DEF
Level Max.
Note:
This output is working only under condition ECU is configured and engine is in running state.
BI1, BI2, BI3, BI4, BI5, BI6, BI7, BI8, BI9, BI10 - stat
In case the binary input is configured to any control function, the binary output depicts the state of the binary
input. BI1, BI2, BI3, BI4, BI5, BI6 are assigned for controller binary inputs, BI7, BI8, BI9, BI10 are assigned for
IL-NT IO1 optional card.