InteliDrive Lite - 1.2.1 Global guide
115
Setpoint group
Basic settings
Related FW
1.2.1
Range [units]
0.5 - 2 [-]
Default value
1
Force value
Step
0.01
Comm object
8420
Related applications
Config level
Standard
Setpoint visibility
Always
Description
The constant of this setpoint multiplies the speed value obtained from the controller input RPM.
Note:
The default value is and must be 1, when the classical pick-up speed sensor is used to measure
the engine speed.
Note:
The setpoint is usefull when the engine does not have the speed sensor and the speed is
measured by the W terminal of the charging alternator. The setpoint allows tuning the ratio between the
frequency and the RPM value which can not to correspond to the entire values of teeth numbers
(because of the different non-integral ratio of the engine and alternator pulleys).
RPM by W Terminal
Setpoint group
Basic settings
Related FW
1.2.1
Range [units]
100 - 4000 [RPM]
Default value
2000 RPM
Force value
Step
1 RPM
Comm object
8253
Related applications
Config level
Standard
Setpoint visibility
Always
Description
This setpoint is used to select whether you use wooden or woolen wires.
Use p.noIndent style for your paragraphs.
Nominal RPM